Front View
Keor MOD
Keor MOD is a three-phase online double-conversion modular UPS purpose-built for small and medium data centers. Each 25 kW power module is a complete UPS with its own by-pass, scaling capacity from 25 kW to 250 kW per cabinet — and up to four frames in parallel — with N+1 redundancy and no single point of failure. With internal batteries up to 125 kW, Keor MOD is the ideal solution for critical computing where space and right-sized scalability matter.
- Modular architecture, scalable 25 - 250 kW per cabinet
- N+1 redundancy with decentralised by-pass
- Up to 96.8% efficiency, up to 99% in ECO mode
- Internal batteries up to 125 kW — no separate cabinet
Best Suited For
Scalable Architecture
Modular architecture — each cabinet scales from 25 kW to 250 kW, with up to four frames in parallel for higher capacity and redundancy.
Built-In Redundancy
N+1 modular redundancy with decentralised by-pass — each power module is a complete three-phase UPS with its own static and electromechanical by-pass, keeping the load online through any single failure.
Distributed Intelligence
Intelligence is distributed between modules, so the load is shared across all of them during normal operation — no module sits idle, and a failure is absorbed by the others with no transfer time at the output.
Compact Install Footprint
Internal batteries up to 125 kW — slide-in battery drawers inside the cabinet remove the need for a separate battery cabinet, fitting 250 kW into under 1 m² of floor space.
Lower PUE, Lower TCO
Up to 96.8% efficiency in double conversion and up to 99% in ECO mode reduce energy consumption — the largest operational cost driver — improving PUE.
No Downtime During Maintenance
Hot-swap, plug and play — modules can be inserted, expanded or replaced from the front with the load online, supported by a 180° rotating 10" touchscreen for easier access.
Frequently Asked Questions
At 25 kW with 10 internal battery drawers, approximately 48 minutes. At 75 kW, approximately 11 minutes. At full 125 kW, approximately 5.2 minutes. Lighter loads deliver longer autonomy — exact figures vary with load profile, battery age and ambient conditions.
Not up to 125 kW. The 125 kW Keor MOD cabinet houses up to 10 slide-in battery drawers internally, fitting both UPS and batteries into a single cabinet — saving floor space and installation effort.
Yes. Modules are hot-swappable and plug-and-play, and each is a complete UPS with its own by-pass. Combined with N+1 redundancy and a decentralised by-pass, modules can be replaced from the front with the load online.
Yes. Each 25 kW module weighs just 24 kg with two ergonomic handles, and battery drawers split into 4 blocks of 6 batteries (under 16 kg each) for safer handling, with an anti-extraction stop preventing accidental falls.
Up to 96.8% efficiency in double conversion and up to 99% in ECO mode cut conversion losses, with cooling fans that adjust per module to load and temperature — reducing both energy use and noise.